SKIL
Controls - Low Pressure Transmitter/Controller Model 222:
Technical Data
Ordering
The SKIL Controls Low Pressure
Transmitter provides an accurate and reliable means of measuring and controlling
low positive, negative and differential pressure.
The model 222 is designed to measure pressure conditions
within combustion plant can be used to control air flow for optimum combustion
efficiency. Specifically designed for boiler, incinerator and furnace
applications, it is equally suitable for any inert gas heating and ventilating
applications, or energy management systems.
Housed in a weatherproof aluminium enclosure to IP
65, the Model 222 incorporates a robust stainless steel variable capacitance sensor with quality solid state circuits providing
accuracy and stability. The unit
complies with current EMC and LUD standards.
The Transmitter is available with pressure ranges of
± 0 –5 mm wg (0 to 0.5 mbar) to ± 0 – 1000 mm
wg
(0 to 100 mbar).
The Model 222 Transmitter will provide an analogue output
signal of 0-10vDC or 0-1 mA or 4-20 mA switch selectable.
The Model 222 Transmitter/Controller will, in addition
to transmitting an electrical signal proportional to pressure, provide
a control or alarm function with the capability of operating an AC motor
or damper actuator within the voltage range of 12 – 240v AC.
The control function utilises solid state relays and
a selectable control filter to provide a time averaging proportional control
facility.

Outstanding features:
Solid State Circuitry - no mechanical parts, providing
high reliability, maintenance free operation.
Robust VRP Transducer - increased sensitivity ideal for flue gas draught
measurement.
Self Contained Transmitter/Controller - reduced installation costs, no
need for interface relays or contactors.
Standard 4-20mA/0-10Vdc - high accuracy and stability for re-transmission
to recorder, logger or EMS.
Solid State Control/Alarm Output - direct switched output to control a.c.
motor/actuator.
Selectable filters - for damping draught fluctuations.

Specification:
Environmental
Enclosure : Diecast aluminium Al Si 12, DIN 1725.
Weatherproof to IP 65 Wall mounting.
Length 180, width 140, height 71, excluding fittings.
Pressure connection: 6mm OD compression fittings
Cable entries: 3 off drilled 20.6mm Dia. For M20 x 1.5 pitch or pq 13.5
Operating temperature : -18°C to 65°C
Weight : 1.5 kg net
Electrical
Supply voltage: 115V or 230Vac ± 10% 50/60 Hz
Analogue output current: 4-20mA or 0-1mA switch
Selectable. Max insertion 600 ohms
Analogue output voltage: 0-10V dc.
Max current 5.0 mA
Damping filter time constant: 0.5 to 5 seconds, switch selectable
Control Board (where fitted)
Control switching output: Solid-state relays, 12-80Vac
or 80-240Vac (see control options) 2 ampere, resistive.
Damping filter time constant: 0.5 to 5 seconds, switch selectable.
Pressure Ranges: 5 to 1000 mm water gauge. Gauge or differential (0.5
mbar 100 mbar)
Pressure Media
Typically air or similar non-conducting gases.
Transducer
Capacitance principle with stainless steel body and
diaphragm and electrode. Ceramic insulator. Internal
temperature compensation.
Performance
Accuracy (see note 1): ±1.2% of full-scale,
at constant temperature
Non-linearity (BFSL) ±1% of full-scale
Hysteresis 0.2% of full-scale
Non-repeatability 0.2% of full-scale
Maximum line pressure 10 PSI in positive or negative direction
Thermal effects:
Zero/span shift 0.1% per °C
Compensated range -18 to +65°C
Warm up shift (see note 2): 0.5% of full-scale total
Note 1: Accuracy expressed ad the root sum squares of
non-linearity, hysteresis and non-repeatability.
Note 2: While internal temperature compensation becomes effective.
Ordering information and
model code:

Key Model Code.
Code: 222
Description: Low Pressure Transmitter/Controller
Supply: 230/115V (selectable) +10% - 15% 50/60 Hz
Output: 0-10V dc standard with 0 to 1mA or 4 to 20mA selectable.
Table 1 - range
| Code |
Description ± Pressure or Differential
Pressure |
| A |
0-5mm W.G. (0 to 0.5 millibar) |
| B |
0-10mm W.G. (0 to 1 millibar) |
| C |
0-20mm W.G. (0 to 2 millibar) |
| D |
0-40mm W.G. (0 to 4 millibar) |
| E |
0-100mm W.G. (0 to 10 millibar) |
| F |
0-200mm W.G. (0 to 20 millibar) |
| G |
0-500mm WG (0 to 50 millibar) |
| H |
0-1000mm WG (0 to 100 millibar) |
Table 2 - control options
| Code |
Description |
| 1 |
Tri-state, solid state relay for control
or
high/low alarm (12 - 80V ac) |
| 2 |
Tri-state, solid state relay for control
or
high/low alarm ( 80 - 240V ac ) |
Go to order form.
Return to Instrumentation